| Plan Review Notes For Permit 03030336 |
| Permit Number |
03030336 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-14 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW WIRE SIZES ON PANEL | | | SCHEDULE FOR ALL BRANCH CIRCUITS. | | | | | | 2)NOTE: PLEASE LIST THE REQ`D SIGN | | | CIRCUIT PER 600-5 | | | | | | 3)NOTE: PLEASE CIRCUIT EM/EXT LTS PER | | | 700-12E. | | | | | | 4)NOTE: PLEASE SIZE OCP FOR AHU HEAT | | | PER 424-3B | | | | | | 5)NOTE: PLEASE SHOW SIZE OF TAPPED | | | CONDUCTORS FROM GUTTER TO METER AND | | | METER TO MAIN DISC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|