2003-03-14 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW WIRE SIZES ON PANEL
 SCHEDULE FOR ALL BRANCH CIRCUITS.
  
 2)NOTE: PLEASE LIST THE REQ`D SIGN
 CIRCUIT PER 600-5
  
 3)NOTE: PLEASE CIRCUIT EM/EXT LTS PER
 700-12E.
  
 4)NOTE: PLEASE SIZE OCP FOR AHU HEAT
 PER 424-3B
  
 5)NOTE: PLEASE SHOW SIZE OF TAPPED
 CONDUCTORS FROM GUTTER TO METER AND
 METER TO MAIN DISC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372