| Plan Review Notes For Permit 03030326 |
| Permit Number |
03030326 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A1, SHOWER SHALL COMPLY WITH | | | SECTION 11-4.21 AND ALL SUBSECTIONS. | | | PLEASE PROVIDE DETAILS. | | | 2) SHT P1 WATER HEATER DETAIL, THE | | | RELIEF VALVE SHALL NOT BE USED AS A | | | MEANS OF CONTROLLING THERMAL EXPANSION. | | | SECTION 504.5. PLEASE SHOW EXPANSION | | | TANK TO COMPLY WITH 607.3.2 | | | 3) BACKFLOW PREVENTOR REQUIRED ON WATER | | | SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|