| Date |
Text |
| 2003-04-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A1 ENLARGED RESTROOM PLAN. LAV TO |
| | BE 1'3" OFF WALL. WATER CLOSET SHALL BE |
| | 17" TO 19" MEASURED TO THE TOP OF THE |
| | TOILET SEAT. 11-4.16.3 |
| | 2) SHT A2 DETAIL #3, LAV TO BE 1'3" OFF |
| | WALL TO CENTER. BREAK ROOM (207) SINK |
| | TO COMPLY WITH 11-4.24 AND ALL SUBSECT- |
| | IONS. PLEASE SUBMIT DETAILS. - PLEASE |
| | SUBMIT DETAILS FOR DRINKING FOUNTAIN TO |
| | SHOW COMPLIANCE WITH 11-4.15 AND ALL SUB |
| | SECTIONS. SHOW CLEAR FLOOR SPACE. |
| | 3) SHT A3 PROVIDE CALCULATIONS FOR PRIM- |
| | ARY AND SECONDARY ROOF DRAINS PER SEC'S. |
| | 1106, & 1107. SHOW 1/2 AREA OF ALL VERT- |
| | ICAL WALLS INCLUDING PARAPETS. INCLUDE |
| | AREAS OF ALL ROOFS DRAINING FROM ABOVE. |
| | SHOW SIZE OF ALL OPENINGS FOR DOWNSPOUTS |
| | - SCUPPER |
| | SHOW SIZE OF ALL DOWNSPOUTS |
| | 4) SHT P1 WILL THERE BE CHEMICALS STORED |
| | AND USED? IF SO MSDS SHEETS WILL BE REQD |
| | AND EMERGENCY SHOWER MAY BE REQUIRED DE- |
| | PENDING ON MSDS SHEETS. |
| | 5) RPZ BACKFLOW REQUIRED ON BLDG WATER |
| | SERVOCE. |
| | 6) SHT P2 WATER HEATER DETAIL. SECTION |
| | 504.2 VACUUM RELIEF REQUIRED. SECTION |
| | 607.3.2 THERMAL EXPANSION CONTROL REQD.' |
| | SECTION 504.5 THE RELIEF VALVE SHALL NOT |
| | BE USED AS MEANS OF THERMAL EXPANSION |
| | CONTROL. |
| | 7) A SERVICE SINK IS REQUIRED PER TABLE |
| | 403.1 (STORAGE) |