2003-03-07 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY CONDUCTOR SIZE
 FROM ELEVATOR DISC, W/ 40A OCP AND #10?
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 INFORMATION REQ`D FOR ENGINEER OF
 RECORD IN TITLE BLOCK.
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW EQUIPMENT. IT IS NOTED THAT AIC
 RATING WERE SUBMITTED FOR PANEL.
 110-9
  
 4)NOTE: PLEASE SUBMIT WIRE SIZE FROM
 MDP TO NEW DISC #5.
  
 5)NOTE: PLEASE PROVIDE LOAD FOR ELEVATOR
 COMBINED WITH LOAD ON PANEL..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372