| Plan Review Notes For Permit 03030306 |
| Permit Number |
03030306 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 BUILDING | | | WPB CITY CODE | | | | | | 1) DO ROOF DRAIN CALCULATIONS INCLUDE | | | 1/2 AREA OF ALL VERTICAL WALLS AND ALL | | | THE AREA OF THE ROOF THAT DRAINS ON TO | | | THE ROOF FROM ABOVE? THIS INFORMATION IS | | | NOT SHOWN AS REQUESTED. | | | 2) SHT A2.2 PROVIDE A DETAIL FOR THE | | | SCUPPERS THAT COMPLY WITH SEC 1503.4.2 | | | 2" MIN AND 4" MAX ABOVE ROOF TO FLOW | | | LINE OF SCUPPER. | | | 3) SHT P-2 CONDENSATE SHALL NOT DRAIN IN | | | TO SANITARY. CONDENSATE SHALL DRAIN TO | | | THE EXTERIOR OF THE BLDG SEPARATELY AND | | | SHALL TIE INTO THE STORM, A CATCH BASIN, | | | OR DRYWELL MINIMUM OF 12" FROM THE BLDG. | | | SECTION 1503.4.4. PLEASE PROVIDE DETAIL. | | | -RESPONSE NOTED - CITY CODE SEC 90-125 | | | PROHIBITS CONDENSATE IN SANITARY SYSTEM. | | | 4) THE 5' TURNING RADIUS SHALL BE UN- | | | OBSTRUCTED - THE DOOR SHALL NOT OPEN IN- | | | TO THE TURNING RADIUS. SECTION 11-4.2.3 | | | THE SPACE FOR A WHEELCHAIR TO MAKE A 180 | | | DEGREE TURN IS A CLEAR SPACE OF 60" | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|