Text |
| 2003-03-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLEASE PROVIDE CALCULATIONS FOR MINI- |
| | MUM FACILITIES. CONFERENCE ROOM AND MUL- |
| | TI PURPOSE ROOM APPEAR TO B ASSEMBLY |
| | WITHOUT FIXED SEATING, AND SHALL BE 7 |
| | NET PER TABLE 1003.1 FBC-2001 |
| | - AREA, NET FLOOR. THE AREA ACTUALLY |
| | OCCUPIED NOT INCLUDING ACCESSORY UN- |
| | OCCUPIED AREAS SUCH AS CORRIDORS, STAIRS |
| | CLOSETS, THICKNESS OF WALLS, COLUMNS, |
| | TOILET ROOM, MECHANICAL AREA OR OTHER |
| | FEATURES. - |
| | 2) TABLE 403.1 A DRINKING FOUNTAIN IS |
| | REQUIRED. ALSO SEE SECTION 410.1 |
| | 3) SHT A2.1 GROUND FLOOR PLAN AND DETAIL |
| | #3, THE DOOR SHALL NOT OPEN INTO THE |
| | 5' UNOBSTRUCTED TURNING CIRCLE. |
| | 4) SHT A2.1 DETAIL #3 PLEASE SHOW CENTER |
| | OF W/C OFF WALL TO BE 1'6" |
| | 5) SHT A2.2 PLEASE PROVIDE CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAIN PER |
| | SECTIONS 1106 & 1107. SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS. |
| | SHOW AREA OF ALL ROOF AREA THAT DRAINS |
| | ON TO ROOF FROM ABOVE. - SCUPPER DETAIL |
| | DOES NOT SHOW SIZE. PROVIDE HEIGHT AND |
| | WIDTH. IF PRIMARY AND SECONDARY (SCUPPER |
| | ARE DRAINING THROUGH THE SAME OPENING, |
| | THEN THE OPENING PROVIDED SHALL BE LARGE |
| | ENOUGH TO DRAIN THE AREA OF EACH. SHOW |
| | SQUARE FOOTAGE DRAINED BY EACH OPENING. |
| | INDICATE WHERE DOWNSPOUTS TERMINATE. |
| | 6) SHT P1 SECTION 606.2 SHUTOFF VALVES |
| | SHALL BE INSTALLED ON THE WATER SUPPLY |
| | PIPE TO EACH SILLCOCK. |
| | 7) SHT P2 CONDENSATE SHALL NOT DRAIN IN- |
| | TO SANITARY. CONDENSATE SHALL DRAIN TO |
| | THE EXTERIOR OF THE BLDG SEPARATELY AND |
| | SHALL TIE INTO STORM, A CATCH BASIN, OR |
| | DRYWELL, MINIMUM OF 12 FROM BLDG. PER |
| | SECTION 1503.4.4 FBC-2001 PLEASE PROVIDE |
| | DETAIL. |
| | |
| | REVIEW BY KEN STEVENS |