| 2003-04-03 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE THE LOCATION AND SIZE OF THE |
| | ATTIC ACCESS TO THE AREA ABOVE THE |
| | MASTER BEDROOM. |
| | |
| | 3) THE ROOF SHEATHING NAIL SPACING GIVEN |
| | ON SHEET GN1 IS INCORRECT. SEE CITY OF |
| | WPB AMENDMENTS TO FBC TABLE 2306.1. |
| | |
| | 4) THE EXTERIOR STUCCO SOFFIT SPECS. #7 |
| | ON A5 STATES THAT METAL LATH IS TO BE |
| | ATTACHED NOT MORE THAN 6" APART. ASTM C |
| | 1063 REQUIRES 3/8" RIB LATH TO BE |
| | ATTACHED AT EVERY RIB (4" O.C.). PLEASE |
| | REVISE. |
| | |
| | 5) THE GIRDER AT THE SECOND FLOOR ABOVE |
| | BEDROOM #2 WITH AN UPLIFT OF 5455# AND |
| | BEARING ON THE (3) 2X6 HAS THE WRONG |
| | CONNECTOR SPECIFIED. SEE SHEET S3. THE |
| | DETAIL THAT IS SPECIFIED SHOWS A USP |
| | USC 53 ATTACHED TO A MASONRY WALL. |
| | NOTE: SOME HOLDOWN STRAPS MAY NOT WORK |
| | AT THIS LOCATION DUE TO PROXIMITY TO THE |
| | CORNER. |
| | |
| | 6) THE TRUSS/GIRDER CONNECTION DETAIL ON |
| | S-3 SHOWS A 2X4 STUD WALL. THE WALL IS |
| | ACTUALLY A 2X6 STUD WALL. PLEASE CORRECT |
| | |
| | 7) SPECIFY THE SPECIAL ROOF SHEATHING |
| | NAILING REQUIREMENTS REQUIRED BY CITY OF |
| | WPB AMENDMENTS TO FBC TABLE 2306.1. |
| | INDICATE FASTNER TYPE, SPACING, AND |
| | ZONES. |
| | |
| | 8) SPECIFY THE LENGTH OR EMBED DEPTH OF |
| | THE 1/2" DIA. EXPANSION ANCHORS AT THE |
| | WD. FRAME TO CONCRETE WALL DETAIL ON A6. |
| | |
| | 9) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALC. FORM. |
| | |
| | 10) THE OPENING SIZES GIVEN ON THE STORM |
| | PANEL SCHEDULE DO NOT MATCH THE WINDOW |
| | SIZES ON THE PLANS FOR NUMBERS 1,2,18 & |
| | 19. NUMBERS 18 & 19 WERE CHANGED BY THE |
| | ARCHITECT TO MEET EGRESS REQUIREMENTS. |
| | ITEM #1 DOES NOT LIST THE HEIGHT OR SPAN |
| | PLEASE CORRECT. |
| | |
| | 11) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR THE GLAZED FRENCH DOOR AT |
| | THE CABANA BATH. |
| | |
| | 12) PROVIDE A SOIL BORING TEST REPORT AS |
| | REQUIRED BY FBC 1804.2.2. |
| | |
| | NOTE: PLEASE RETURN ALL OLD SHEETS OF |
| | DRAWINGS WHEN RESUBBING NEW PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |