Plan Review Notes
Plan Review Notes For Permit 03030165
Permit Number 03030165
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-03-21 00:00:001) DOOR # 9 SHALL BE AT LEAST 45 MINUTE
 FIRE RATED SINCE IT IS WITHIN A ONE
 HOUR FIRE WALL.
  
 2) SINCE NO SPRINKLERS ARE PRESENT,
 THE MECHANICAL AND STORAGE ROOM SHALL
 BE AT LEAST ONE HOUR FIRE RATED WITH
 PROPER OPENING PROTECTIVES.
  
 3) FUEL TANK WORK SHALL COMPLY WITH
 NFPA 30.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910