| Plan Review Notes For Permit 03030165 |
| Permit Number |
03030165 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-21 00:00:00 | 1) DOOR # 9 SHALL BE AT LEAST 45 MINUTE | | | FIRE RATED SINCE IT IS WITHIN A ONE | | | HOUR FIRE WALL. | | | | | | 2) SINCE NO SPRINKLERS ARE PRESENT, | | | THE MECHANICAL AND STORAGE ROOM SHALL | | | BE AT LEAST ONE HOUR FIRE RATED WITH | | | PROPER OPENING PROTECTIVES. | | | | | | 3) FUEL TANK WORK SHALL COMPLY WITH | | | NFPA 30. | | | | | | 4) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|