| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FS/ FAC, 61G15-23.002 | | | 471.025, TITLE BLCOK FOR ENGINEER OF | | | RECORD SHALL BE ON ALL SHEETS. | | | | | | 2)NOTE: PLEASE SEE 700-12E FOR CIRCUIT- | | | ING OF EM / EXT LTS. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT, INCLUDING NEW MAINS. | | | 110-9/215-5 | | | | | | 4)NOTE: PLEASE SEE RISER DIAGRAM, IT IS | | | NOTED THAT AN EQUIPMENT GROUNDING | | | CONDUCTOR IS TO BE INSTALLED BETWEEN | | | GUTTER AND MAIN DISC'S. PLEASE SHOW AN | | | EQP, GRD IS ONLY INSTALLED AFTER FIRST | | | MEANS OF DISC. PER 250-24 PLEASE CORRECT | | | | | | 5)NOTE: PLEASE CLARIFY LOCATION OF NEW | | | RECEPT, APPEARS TO BE SERVICE BAY AREA? | | | PLEASE PROVIDE TYPE OF LOCATION ON PLAN | | | PER ART 500. NEC. | | | | | | 6)NOTE: PLEASE SHOW LOCATION OF SERVICE | | | ON PLANS , INCLUDING LOCATIONS OF NEW | | | AND EXISTING PANELS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|