| Date |
Text |
| 2003-04-02 00:00:00 | **********CORRECTIONS************ |
| | |
| | 1.) BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE ACTUAL PERMIT PLANS |
| | MUST BE STAMPED BY THAT OFFICE, AND A |
| | COPY OF THE PAID RECEIPT ATTACHED TO |
| | THE PERMIT APPLICATION.PLEASE CALL |
| | (561) 233-5025 FOR MORE INFORMATION. |
| | |
| | 2.)PER FBC 104.3.1.1, MINIMUM PLAN |
| | REVIEW CRITERIA, PROVIDE A ROOF FRAMING |
| | PLAN. ELEVATIONS CONFLICT WITH SECTIONS. |
| | |
| | 3.)PLEASE PROVIDE AREA CALCULATIONS |
| | OF EXISTING HOUSE AND ADDITION AREA. |
| | |
| | 4.)2304.3.4 WOOD JOIST SHALL HAVE 18" |
| | CLEARANCE FROM THE BOTTOM OF JOIST TO |
| | EARTH OR ELSE BE PRESSURE TREATED WOOD. |
| | |
| | 5.)1403.1.6 IN ORDER TO PROVIDE FOR |
| | INSPECTION FOR TERMITE INFESTATION, |
| | CLEARANCE BETWEEN EXTERIOR WALL COVER- |
| | INGS AND FINAL EARTH GRADE ON THE |
| | EXTERIOR OF A BUILDING SHALL NOT BE LESS |
| | THAN 6 INCHES. |
| | |
| | 6.)PROVIDE ENERGY CALCS FOR ADDITION |
| | AREA. |
| | |
| | 7.)FBC 905.2, SMOKE DETECTOR REQUIRED. |
| | |
| | 8.)PROVIDE LEGIBLE PRODUCT APPROVALS |
| | FOR THE FOLLOWING ITEMS: |
| | A.)HURRICANE SHUTTERS (CAN'T READ) |
| | B.)FRENCH DOORS (CAN'T READ) |
| | C.)WINDOW |
| | D.)LAP SIDING |
| | |
| | 9.) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 |