| Plan Review Notes For Permit 03030105 |
| Permit Number |
03030105 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | PROVIDE A RISER DIAGRAM WITH LOAD | | | CALCULATIONS SHOWING ADDITIONAL | | | LOADS.SHOW HOW THE NEW 60 AMP PANEL IS | | | BEING FED,AND AMPERAGE OF EXISTING SVC. | | | | | | ADD RECEPTACLES TO COMPLY WITH 210-52. | | | | | | NOTE THE WATER HEATER IN THE CLOSET MUST | | | COMPLY WITH 422-17 NEC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|