| 2003-04-29 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | MODEL C (REVERSE) |
| | |
| | 1) SHEET S2, ROOF FRAMING PLAN.THE |
| | GIRDER TRUSS ANCHOR MARK 3, ABOVE |
| | BATH 2, HAS AN UPLIFT CAPACITY OF 1300# |
| | (SEE SHEET S3, CONNECTORS SCHEDULE) |
| | WHICH IS LESS THAN THE STATED UPLIFT |
| | (U=1706#).AMEND THE PLANS. |
| | |
| | 2) SHEET S1, SECOND FLOOR FRAMING.THE |
| | TWO FLOOR GIRDER ANCHORS MARK 6, |
| | SPECIFIED AT THE WOOD POST BETWEEN THE |
| | KITCHEN AND DINING ROOM, HAVE A COMBINED |
| | UPLIFT CAPACITY OF 2970# (SEE SHEET S3, |
| | CONNECTORS SCHEDULE) WHICH IS LESS THAN |
| | THE STATED UPLIFT (U=3152#).AMEND THE |
| | PLANS. |
| | |
| | 3) SHEET S3, CONNECTOR SCHEDULE. SIMPSON |
| | HETAL 20 (CONNECTOR MARK 9) REQUIRES |
| | 20-10D X 1-1/2" NAILS TO THE TRUSS AND |
| | SIMPSON HGT 2 (CONNECTOR MARK 12) |
| | REQUIRES 16D NAILS TO THE GIRDER.AMEND |
| | THE SCHEDULE. |
| | |
| | 4) FBC 1007.3.1 STAIR TREADS AND RISERS. |
| | ADD NOTES TO SHEET A1.01 TO STATE THE |
| | RISER HEIGHT (MUST BE BETWEEN 7.5" AND |
| | 7.75" WITH THE STATED 9" TREAD) AND TO |
| | SPECIFY A NOSING.EVERY TREAD LESS THAN |
| | 10" WIDE SHALL HAVE A NOSING OR |
| | EFFECTIVE PROJECTION OF APPROX. 1" OVER |
| | THE LEVEL IMMEDIATELY BELOW THAT TREAD. |
| | |
| | 5) FBC 607SHEET A0.01, NOTE 15 STATES |
| | THAT THE CONSTRUCTION IS TYPE III.THE |
| | CONSTRUCTION IS TYPE V.AMEND THE PLAN. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |