| Plan Review Notes For Permit 03022362 |
| Permit Number |
03022362 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-04 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, PLEASE | | | SEE CONDUCTORS LEAVING BOTTON OF PANEL | | | AND GOING TO?? 3-#1'S ETC?? | | | | | | 2)NOTE: PLEASE SEE CONDUCTORS SHOWN ON | | | PANEL SCHEDULE AS FEEDERS, PLEASE SEE | | | 250-24, AN EQUIPMENT GROUND IS ONLY | | | INSTALLED AFTER THE FIRST MEANS OF DISC. | | | | | | 3)NOTE: PLEASE 210-52-C-3 FOR MISSING | | | GFI ON PENINSULAR. | | | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | | ONLY ONE EXTS SMALL APPLIANCE CIRCUIT. | | | PLEASE SEE 210-11-C1 | | | | | | 5)NOTE: IF THIS IS A NEW SERVICE, PLEASE | | | SUBMIT AIC RATING OF NEW MAIN, ALL | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|