2003-03-04 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, PLEASE
 SEE CONDUCTORS LEAVING BOTTON OF PANEL
 AND GOING TO?? 3-#1'S ETC??
  
 2)NOTE: PLEASE SEE CONDUCTORS SHOWN ON
 PANEL SCHEDULE AS FEEDERS, PLEASE SEE
 250-24, AN EQUIPMENT GROUND IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC.
  
 3)NOTE: PLEASE 210-52-C-3 FOR MISSING
 GFI ON PENINSULAR.
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS
 ONLY ONE EXTS SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210-11-C1
  
 5)NOTE: IF THIS IS A NEW SERVICE, PLEASE
 SUBMIT AIC RATING OF NEW MAIN, ALL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  