2003-03-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03022362
 ADD: 334 HUNTER ST
 CONT: O/B ANDERSON GEORGE
 TEL: (561)585-1301
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET 3.1 GENERAL NOTES (1) PLANS
 INDICATE THAT THE WORK SHALL COMPLY WITH
 THE STANDAERD BUILDING CODE. WE ARE
 CURRENTLY USING THE 2001 FLORIDA BUILD-
 ING CODE.
  
 2) NOTE 12 INDICATES THE USE OF DEAD
 BOLTS FOR EXTERIOR DOORS. 1012.7 DOUBLE
 CYLINDER DEAD BOLTS ARE PROHIBITED ON
 REQUIRED MEANS OF EGRESS DOORS.
  
 3) MISSING PRODUCT TESTING REPORTS FOR
 THE EXTERIOR DOORS 001 & 003. THE CITY
 ACCEPTS S.B.C.C.I. REPORTS OR DADE
 COUNTY PRODUCT ACCEPTANCE REPORTS.
  
 4) SHEET 4.1 INDICATES THE BEAM 8"X22"
 BEING CUT DOWN TO 8"X12". WHEN CUTTING
 THE BEAM IN HALF WHAT STEEL WILL REPLACE
 THE BOTTOM TENSION STEEL?
  
 5) SHEET 3.1 INDICATES A NEW (3) 2X12
 WOOD BEAM TO SIT ON THE EXISTING TIE
 BEAM (EXTERIOR WALL). SHEET 4.1 DETAIL
 (3) INDICATES THAT IT SITS ON TOP OF THE
 TIE BEAM. HOW DOES THE DROP CEILING AT
 7'-6" ATTACH TO THIS NEW BEAM? SEE
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026