2003-06-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03022336
 ADD: 360 GREGORY ROAD
 CONT: TREND WEST INC
 TEL: (561)358-8817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: REVIEWED/ PROVISO
  
 1) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 2)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 FOOR FRAMING INSPECTION.HIGH VALUES FOR:
 TA-18R
 (2) TA 18R
  
 3) ALL OPENINGS TO BE LARGE MISSLE
 IMPACT GLAZING, IF CONTRACTOR WISHES TO
 USE NON-IMPACT RATED GLAZING STORM
 SHUTTERS UNDER A SEPERATE PERMIT WILL
 BE REQUIRED BEFORE A CERTIFICATE OF
 OCCUPANCY WILL BE ISSUED.
  
 JIM WITMER
 (561) 659-8096 X 8412