2003-05-16 00:00:00************** UNSAT ******************
  
 PLEASE NOTE, SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO NOTE, DUE TO CHANGES MADE
 FROM COMMENT FROM FIRST REVIEW, THERE
 ARE NOW ADDTIONAL COMMENTS.
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULE. RISER SHOWS 200A
 PANEL AND PANEL IS SHOWN AS 150A.?
  
 2)NOTE: PLEASE SEE 110-26 FOR CLEARENCE
 REQ`MENTS ABOUT ELECTRICAL EQUIPMENT.
 PLEASE ALSO SEE 384-7,8
 PANEL SCHEDULE MENTIONS ON UPPER LEFT-
 HAND CORNER THAT PANEL LOCATION IS IN
 GARAGE AND PLAN SHOWS CLOSET? PANEL DOES
 NOT MEET 110-26 FOR CLEARENCE, 3FT OUT
 AND 30" WIDE. AND IN CLOSET.
  
 3)NOTE: PLEASE SEE RECEPT SPACING ALONG
 KITCHEN COUNTERSPACE. PLEASE SEE 210-52,
 C-1.
  
 4)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING THROUGH-OUT HOUSE, THERE ARE
 A COUPLE MISSING. 2' OF WALL SPACE AND
 UPPER LEVEL ALSO.
  
 PLEASE SEE LETTER ATTACHED FOR DESIGNER
 OF RECORD. REQ`D BY FS 553.80(2)(B)
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE TAKE OUT OLD/VOIDED SHEETS AND
 INSERT NEW INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING. OLD SHEETS MAY BE
 PUT IN ONE SEPARATE SET FOR REF.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW