2003-05-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03022336
 ADD: 360 GREGORY RD
 CONT: TREND WEST
 TEL: (561)358-8817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 4)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 5) THE REVISD TRUSS ANCHOR SCHEDULE IN-
 DICATES THE USE OF USP PRODUCTS, THESE
 PRODUCTS ARE NOT REPRESENTED IN THE 2003
 CATALOG, SOME OF THESE ITEMS ARE REFLECT
 ED ON THE PRODUCTS BEING DISCONTINUED,
 NOLONGER IN THE CATALOG AND THEREFORE
 THE REDUCED VALUES ARE NOT GIVEN.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 6)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026