Plan Review Notes For Permit 03022336
Permit Number 03022336
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE ANY NECESSARY
 CORRECTION TO PLANS AND RESUBMIT FOR
 REVIEW.
  
 1}THE GROUNDING ELECTRODE CONDUCTOR
 SHOULD BE #4CU PER 210-66,THE RISER
 DIAGRAM SHOWS #6.
  
 2}THE #1/0 FEEDERS SHOWN ON THE RISER
 ARE NOT SUFFICIENT FOR A 200 AMP
 SERVICE. TABLE 310-15(B)(6).
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} PLEASE NOTE KITCHEN COUNTERTOP
 RECEPTACLES MUST MEET 210-52.
  
 5} PANEL "A" MUST HAVE CLEARANCES PER
 110-26.
  
 6} MASTER BEDROOM SPACING MUST COMPLY
 WITH 210-52,PLEASE CHECK SPACING.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELELCTRICAL PLAN REVIEW
 561/659-8096 EXT.8392