| 2003-03-18 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION MAKE ANY NECESSARY |
| | CORRECTION TO PLANS AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1}THE GROUNDING ELECTRODE CONDUCTOR |
| | SHOULD BE #4CU PER 210-66,THE RISER |
| | DIAGRAM SHOWS #6. |
| | |
| | 2}THE #1/0 FEEDERS SHOWN ON THE RISER |
| | ARE NOT SUFFICIENT FOR A 200 AMP |
| | SERVICE. TABLE 310-15(B)(6). |
| | |
| | 3} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4} PLEASE NOTE KITCHEN COUNTERTOP |
| | RECEPTACLES MUST MEET 210-52. |
| | |
| | 5} PANEL "A" MUST HAVE CLEARANCES PER |
| | 110-26. |
| | |
| | 6} MASTER BEDROOM SPACING MUST COMPLY |
| | WITH 210-52,PLEASE CHECK SPACING. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELELCTRICAL PLAN REVIEW |