| Plan Review Notes For Permit 03022335 |
| Permit Number |
03022335 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-08-25 00:00:00 | **************** UNSAT ************* | | | | | | PLEASE SEE NOTES SET FORTH FROM ORIGINAL | | | PROVISO. PLEASE SEE THAT SOME ITEMS | | | WERE NOT CORRECTED. | | | | | | 1)NOTE: PLEASE SEE 250-66 FOR GROUNDING | | | ELECTRODE CONDUCTOR. ONE SHOWN AT #4, | | | OTHER SHOWN AT #6.? | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN DISCONNECT | | | TO PANEL. 250-24/250-122 | | | | | | 3)NOTE: PLEASE SEE MISSING FRONT AND | | | REAR RECEPTS. 210-52E | | | | | | 4)NOTE: PLEASE SEE MISSING BATH RECEPT | | | FOR BATH / POWDER RM. 210-52D | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|