| 2003-09-15 00:00:00 | *****CORRECTIONS***** |
| | *****REVISION****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)ADDITIONAL FEES DUE, $36.26. |
| | BZ#230485 ATTACHED; PLEASE PAY AT |
| | CASHIER (INCREASED VALUE, RADON). |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 3.)THE MINIMUM WALL INSULATION AS PER |
| | THE ENERGY CALCS SUBMITTED IS R5. REVISE |
| | ALL APPLICABLE DETAILS, INCLUDING |
| | WINDOW JAMB A2, STEMWALL SECTION A4, |
| | WALL SECTION A4. |
| | |
| | 4.)ON THE WALL SECTION, A4, LOWEST |
| | BUILDING FLOOR ELEVATION SHALL BE A MIN. |
| | 4" ABOVE FINISHED GRADE, CITY OF WEST |
| | PALM BEACH AMENDMENTS FBC1804.1.7. |
| | |
| | 5.)WALL SECTION, A4, BOTTOM OF FOOTER |
| | IS REQUIRED TO BE A MINIMUM OF 12" BELOW |
| | FINISHED GRADE, FBC1804.1.3. |
| | |
| | 6.)A5, USP TRUSS TIE DOWN SCHEDULE, |
| | UPLIFT ON SCHEDULE EXCEEDS MAXIMUM |
| | IN USP 2003 CATALOG FOR RT-T CONNECTORS. |
| | TARP HAS BEEN DISCONTINUED.RT-T IS |
| | A WOOD-TO-WOOD CONNECTOR AND CANNOT BE |
| | USED IN A WOOD-TO-MASONRY APPLICATION. |
| | THIS PERMIT WAS ISSUED WITH A PROVISO |
| | TO SUBMIT A NEW ATTACHMENT SCHEDULE. |
| | REVISE THE ATTACHMENT SCHEDULE, AND |
| | SPECIFY ALL ATTACHMENTS INCLUDING |
| | GIRDERS. |
| | |
| | 7.)THE ROOF PLAN A5, AND THE KNEE WALL |
| | SECTION REFER TO A "LONG FLAT STRAP". |
| | SPECIFY WHICH STRAP IS TO BE USED. |
| | |
| | 8.) THE PLANS SHOW EXISTING ROOF TRUSSES |
| | AND GIRDERS WHICH ARE TO BE RELOCATED. |
| | BE ADVISED THAT TRUSS ENGINEERING MUST |
| | BE PROVIDED AT THE TIME OF INSPECTION, |
| | INCLUDING THE EXISTING TRUSSES BEING |
| | RELOCATED. |