| Plan Review Notes For Permit 03022335 |
| Permit Number |
03022335 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-05 00:00:00 | ************PROVISO/REVISE ************ | | | | | | PLANS STILL MISSING THE FOLLOWING AND | | | NEED TO BE REVISED BEFORE FINAL. | | | | | | 1)NOTE: PLEASE SHOW SD`S INSIDE AND | | | OUTSIDE BEDROOM. NFPA-72 8-1.4.2 | | | | | | 2)NOTE: PLEASE SHOW EQUIPMENT GROUNDING | | | CONDUCTOR BETWEEN MAIN DISC AND PANEL. | | | 250-24/250-122 | | | | | | 3)NOTE: PLEASE SHOW ALL KITCHEN COUNTER- | | | -SPACE RECEPTS AS GFI/GFI PROTECTED. | | | 210-8-A-6 | | | | | | 4)NOTE: PLEASE SEE MISSING REAR RECEPT | | | PER 210-52E. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE FINAL. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|