| 2003-04-02 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | MODEL E (REVERSE) |
| | |
| | 1) SHEET S-1, FOUNDATION PLAN AND ROOF |
| | FRAMING PLAN ARE OPPOSITE HAND TO THE |
| | REMAINING PLANS IN THE PLAN SET. |
| | |
| | 2) SHEET S-1, ROOF FRAMING PLAN.ADD A |
| | KEY, FOR THE TRUSS ANCHOR REFERENCE |
| | ANNOTATION, TO CONFIRM IF1MEANS |
| | CONNECTOR MARK1, AND IF 'U' IS THE |
| | DESIGN UPLIFT CAPACITY REQUIRED.WHAT |
| | IS THE VALUE STATED AS 'R', IS IT THE |
| | REQUIRED LATERAL LOAD CAPACITY (EITHER |
| | F1 OR F2)? |
| | REF11IS USED AT THE REAR OF THE |
| | HOUSE, WHAT ANCHOR TYPE IS IT, AND WILL |
| | IT HAVE SUFFICIENT CAPACITY FOR THE HIP |
| | JACK SHOWN AT THE TOP RIGHT OF THE PLAN. |
| | |
| | 3) SHEET S-2, CONNECTOR SCHEDULE.AMEND |
| | THE SCHEDULE TO INCLUDE THE UPLIFT AND |
| | THE LATERAL LOAD CAPACITY FOR THE |
| | SELECTED ANCHORS AND LUMBER GRADE. |
| | |
| | 4) FBC TABLE 600THE GLASS BLOCK WINDOW |
| | IS ON THE PROPERTY LINE.AMEND THE |
| | PLANS TO SHOW THE REQUIREMENT FOR A ONE- |
| | HOUR FIRE-RATED ASSEMBLY. |
| | |
| | 5) SHEET S3, PLYWOOD NAILING DETAIL. |
| | AMEND '10/32 CDX PLYWOOD' TO READ |
| | '19/32 CDX PLYWOOD'. |
| | |
| | 6) PROVISO - ROOF TILE PRODUCT APPROVAL |
| | NOA# 99-1012.02 HAS EXPIRED.SUBMIT A |
| | CURRENT PRODUCT APPROVAL. |
| | |
| | 7) PROVISO - OUTSWING STEEL DOUBLE DOOR |
| | PRODUCT APPROVAL NOA# 99-0311.03 HAS |
| | EXPIRED.SUBMIT A CURRENT PRODUCT |
| | APPROVAL. |
| | |
| | 8) PROVISO - ALUMINUM SLIDING GLASS DOOR |
| | PRODUCT APPROVAL NOA# 98-1228.01 HAS |
| | EXPIRED.SUBMIT A CURRENT PRODUCT |
| | APPROVAL. |
| | |
| | 9) INFORMATIVE - ALUMINUM TUBE MULLION |
| | PRODUCT APPROVAL NOA# 99-0310.01 HAS |
| | EXPIRED.NOT REQUIRED FOR THIS PERMIT |
| | APPLICATION (MODEL E). |
| | |
| | 10) PROVISO - SINGLE HUNG WINDOW PRODUCT |
| | APPROVAL NOA# 98-1222.02 HAS EXPIRED. |
| | SUBMIT A VALID PRODUCT APPROVAL. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |