Plan Review Notes For Permit 03022221
Permit Number 03022221
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-27 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE OCP AND WIRE SIZES ON
 THE PANEL SCHEDULE DO NOT CORRELATE WITH
 THE RISER.
  
 2} THE TITLE BLOCK DOES NOT CONTAIN THE
 FIRM LICENSE NUMBER PER 61G1-16.004(2).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW