| Plan Review Notes For Permit 03022221 |
| Permit Number |
03022221 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-27 00:00:00 | FAILED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SEE THE OCP AND WIRE SIZES ON | | | THE PANEL SCHEDULE DO NOT CORRELATE WITH | | | THE RISER. | | | | | | 2} THE TITLE BLOCK DOES NOT CONTAIN THE | | | FIRM LICENSE NUMBER PER 61G1-16.004(2). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|