| 2003-03-13 00:00:00 | **************** NOTES ************ | | | | | | 1)NOTE: PLEASE SEE MISSING SD`S IN ALL | | | REQ`D LOCATIONS IN HOUSE. REDLINED ON | | | PLANS, PER NFPA-72 8-1.4.2 | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUND BETWEEN MAIN PANEL AND SUB PANEL | | | 250-122 | | | | | | PLEASE REVISE PLANS BEFORE ROUGH. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|