| 2003-02-28 00:00:00 | **********CORRECTIONS************ | | | | | | 1.)PLEASE CONFIRM THAT EVERY CLASSROOM | | | INDICATED ON THE PLAN HAS A DOOR TO | | | THE OUTSIDE AS PER FBC 1005.4.2. | | | | | | 2.)PROVIDE TWO COPIES OF PRODUCT | | | APPROVALS FOR THE MULLIONS TO BE | | | USED BETWEEN THE WINDOW AND DOOR. | | | | | | 3.)PLEASE MARK THE COMPONENTS | | | SELECTED FOR THE PROPOSED INSTALLATION | | | AS PER NOTICE OF ACCEPTANCE 6.1.2 | | | (DUPLICATE COPIES NOT REQUIRED; MARK | | | ON BOTH COPIES ALREADY SUBMITTED). | | | | | | 4.)PLEASE NOTE PRODUCT LIMITATION | | | 3.2 OF THE NOTICE OF ACCEPTANCE; CONFIRM | | | ON THE PLAN THAT THE PROPOSED | | | INSTALLATION FALLS WITHIN THE | | | LIMITATION NOTED. | | | | | | 5.)PLEASE SUBMIT TWO COPIES OF | | | PRODUCT APPROVALS FOR THE LOUVERED | | | DOOR WITH ATTACHMENTS CLEARLY MARKED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | LEA SMITH OR SAMANTHA THYNG | | | 561-659-8096, EXTENSION 8340 |
|