| 2003-03-17 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATIONAND RESUBMIT FOR REVIEW. | | | | | | 1} THE GEC IS INCORRECT FOR 300 AMP. | | | SERVICE,SEE 250-66. | | | | | | 2} HOW IS THE 2ND DISCONNECT BEING FED? | | | PLANS SHOW A CONDUIT TO ONE WITH 6 | | | WIRES, PLEASE CLARIFY. | | | | | | 3} A LAUNDRY CIRCUIT MUST BE CALCULATED | | | PER 220-16(B). | | | | | | 4} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 5} PLEASE SHOW GARAGE RECEPTACLES TO | | | COMPLY WITH 210-8. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|