Notes
Date Text
2003-03-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONAND RESUBMIT FOR REVIEW.
  
 1} THE GEC IS INCORRECT FOR 300 AMP.
 SERVICE,SEE 250-66.
  
 2} HOW IS THE 2ND DISCONNECT BEING FED?
 PLANS SHOW A CONDUIT TO ONE WITH 6
 WIRES, PLEASE CLARIFY.
  
 3} A LAUNDRY CIRCUIT MUST BE CALCULATED
 PER 220-16(B).
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE SHOW GARAGE RECEPTACLES TO
 COMPLY WITH 210-8.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392