| Plan Review Notes For Permit 03022105 |
| Permit Number |
03022105 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-27 00:00:00 | **********CORRECTIONS************ | | | | | | 1.)PREINSPECTION REQUIRED, ALL TRADES. | | | CALL 659-8096 EXT 8404 TO SCHEDULE. | | | | | | 2.)ENGINEER TO VERIFY THE INTEGRITY | | | OF THE EXISTING FIRE WALL. | | | | | | 3.)RE: SECTION A-A, 5/8" TYPE X GYPSUM | | | WALLBOARD REQUIRED AT EACH SIDE OF THE | | | FIRE WALL AS PER FBC704.4.2. | | | | | | 4.)DOUBLE 30# UNDERLAYMENT REQUIRED | | | FOR ROOF AS PER FBC 1507.3.8. | | | | | | 5.)NAILING OF SHEATHING IN ZONE 3 | | | (EDGE)TO BE 4" EDGES AND 6" INTERMEDIATE | | | AS PER WPB AMENDMENTS TO THE FLORIDA | | | BUILDING CODE. | | | | | | 6.)PRODUCT APPROVALS ARE REQUIRED | | | FOR THE WINDOW MULLIONS AND THE ROOF | | | COVERING.PLEASE SUBMIT TWO COPIES OF | | | EACH. | | | | | | 7.)CLARIFY NUMBER OF BOLTS REQUIRED | | | FOR WALL FRAMING - 6' OC MINIMUM.ALSO | | | REQUIRES 7" EMBEDMENT PER FBC 2307.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | LEA SMITH OR SAMANTHA THYNG | | | 561-659-8096, EXTENSION 8340 | | | | | | REVIEWED 2/27/03 BY LEA SMITH |
|