Plan Review Notes
Plan Review Notes For Permit 03022105
Permit Number 03022105
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-27 00:00:00**********CORRECTIONS************
  
 1.)PREINSPECTION REQUIRED, ALL TRADES.
 CALL 659-8096 EXT 8404 TO SCHEDULE.
  
 2.)ENGINEER TO VERIFY THE INTEGRITY
 OF THE EXISTING FIRE WALL.
  
 3.)RE: SECTION A-A, 5/8" TYPE X GYPSUM
 WALLBOARD REQUIRED AT EACH SIDE OF THE
 FIRE WALL AS PER FBC704.4.2.
  
 4.)DOUBLE 30# UNDERLAYMENT REQUIRED
 FOR ROOF AS PER FBC 1507.3.8.
  
 5.)NAILING OF SHEATHING IN ZONE 3
 (EDGE)TO BE 4" EDGES AND 6" INTERMEDIATE
 AS PER WPB AMENDMENTS TO THE FLORIDA
 BUILDING CODE.
  
 6.)PRODUCT APPROVALS ARE REQUIRED
 FOR THE WINDOW MULLIONS AND THE ROOF
 COVERING.PLEASE SUBMIT TWO COPIES OF
 EACH.
  
 7.)CLARIFY NUMBER OF BOLTS REQUIRED
 FOR WALL FRAMING - 6' OC MINIMUM.ALSO
 REQUIRES 7" EMBEDMENT PER FBC 2307.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 LEA SMITH OR SAMANTHA THYNG
 561-659-8096, EXTENSION 8340
  
 REVIEWED 2/27/03 BY LEA SMITH