| Date |
Text |
| 2003-04-01 00:00:00 | PROVISO |
| | ~~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | TO THE PLANS AND RESUBMIT FOR REVIEW |
| | PRIOR TO CALLING ROUGH ELECTRICAL |
| | INSPECTION. |
| | |
| | 1} INDICATE THE SIZE OF THE RISER MAST |
| | AND WIRE TYPE AND SIZE.NOTE THE SERVICE |
| | MUST BE AT LEAST 250 AMPS,#4/0 PER |
| | 310-15 (B)(6). |
| | |
| | 2} THE SIZE OF THE GROUNDING ELECTRODE |
| | CONDUCTOR MUST COMPLY WITH 250-66.(#2 |
| | FOR #4/0 FEEDERS.) |
| | |
| | 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| | COMPLY WITH 250-50(A)(2). TWO GROUND |
| | RODS. |
| | |
| | 4} PANEL SCHEDULES MUST COMPLY WITH |
| | 220-16(A) FOR SMALL APPLIANCES,2@1500 |
| | VA. |
| | |
| | 5} THE LAUNDRY CIRCUIT MUST COMPLY WITH |
| | 220-16(B),1500 VA.PLEASE ADD CORRECT |
| | CALCULATIONS TO PANEL SCHEDULES AND |
| | RECALCULATE LOADS. |
| | |
| | 6} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392 |