2003-04-01 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS AND RESUBMIT FOR REVIEW
 PRIOR TO CALLING ROUGH ELECTRICAL
 INSPECTION.
  
 1} INDICATE THE SIZE OF THE RISER MAST
 AND WIRE TYPE AND SIZE.NOTE THE SERVICE
 MUST BE AT LEAST 250 AMPS,#4/0 PER
 310-15 (B)(6).
  
 2} THE SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR MUST COMPLY WITH 250-66.(#2
 FOR #4/0 FEEDERS.)
  
 3} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250-50(A)(2). TWO GROUND
 RODS.
  
 4} PANEL SCHEDULES MUST COMPLY WITH
 220-16(A) FOR SMALL APPLIANCES,2@1500
 VA.
  
 5} THE LAUNDRY CIRCUIT MUST COMPLY WITH
 220-16(B),1500 VA.PLEASE ADD CORRECT
 CALCULATIONS TO PANEL SCHEDULES AND
 RECALCULATE LOADS.
  
 6} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  