| Plan Review Notes For Permit 03021976 |
| Permit Number |
03021976 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-05 00:00:00 | **********CORRECTIONS************ | | | | | | 1.)PLANS NOT SEALED.PLEASE SUBMIT | | | NEW SEALED PLANS. | | | | | | 2.)SPAN INDICATED ON YOUR STRUCTURAL | | | UPRIGHT SPACING CHART (7') DOES NOT | | | MATCH THE PLAN GIVEN (8').PLEASE NOTE | | | MAXIMUM UPRIGHT SPACING ON THE CHART. | | | THE SPACING FOR 8' SPAN RANGES FROM 5'3" | | | TO 6'4", DEPENDING ON OVERHANG.THE | | | UPRIGHT SPACING SHOWN ON YOUR PLAN IS | | | 7'.PLEASE CLARIFY. | | | | | | 3.)GIVE THE OVERHANG DIMENSION ON | | | THE PLAN - SPACING OF UPRIGHTS VARIES | | | ACCORDING TO OVERHANG SIZE. | | | | | | 4.)INDICATE THE PANEL/SKIN SIZE ON | | | EITHER THE PLAN OR MARK ON THE CHART. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | LEA SMITH OR SAMANTHA THYNG | | | 561-659-8096, EXTENSION 8340 |
|