Plan Review Notes
Plan Review Notes For Permit 03021865
Permit Number 03021865
Review Stop B
Sequence Number 2
Notes
Date Text
2003-05-06 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS AS
 REQUIRED BY CHAPTER 13 OF THE FBC.
  
 4) PROVIDE AN ADDITIONAL COPY OF THE
 SURVEY.
  
 5) SUBMIT AN ADDITIONAL COPY OF THE
 PRODUCT APPROVAL FOR THE POMA BAHAMA
 SHUTTERS. PROVIDE A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. INDICATE THE TYPE OF STORM PANEL
 THAT WILL BE INSTALLED AT EACH OPENING.
  
 6) SHEET A1 INDICATE THAT ALL WINDOWS
 ARE SINGLE HUNG (SH),HOWEVER, NO
 PRODUCT APPROVALS FOR SINGLE HUNG
 WINDOWS WERE SUBMITTED. THE PRODUCT
 APPROVALS THAT WERE SUBMITTED ARE FOR
 HORIZONTAL SLIDING WINDOWS (HS) AND
 CASEMENT WINDOWS (CSMT).
  
 7) ITEM #10 ON PREVIOUS REVIEW WAS NOT
 ADDRESSED. IDENTIFY ON THE PLANS THE
 EXISTING ROOMS THAT ARE ADJACENT TO THE
 ADDITION.
  
 8) INDICATE ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB IS REQUIRED TO BE
 SUPPORTED ON APPROVED MATERIALS AT A
 MAXIMUM OF 3 FEET O.C. PER FBC 1909.3.
  
 9) THE FOOTER SPECS ON A1 SPECIFY THREE
 #5 REINFORCING BARS IN THE FOOTER AND
 THE WALL SECTION ON A2 SPECIFIES TWO
 #5 BARS. PLEASE CLARIFY.
  
 10) THE WALL SECTION ON A2 SPECIFIES
 MTSM 20 TRUSS CONNECTORS AT THE NEW TIE
 BEAM AND THE ROOF FRAMING PLAN ON A1
 CALLS FOR HETAL 20 CONNECTORS AT THE
 NEW BEAM AND MSTM 20 CONNECTORS AT THE
 EXISTING TIE BEAM. THE HETAL 20 CAN BE
 INSTALLED INTO THE CONCRETE WHEN THE
 NEW BEAM IS POURED AND THE MSTM 20 CAN
 BE USED AT THE EXISTING BEAM. PLEASE
 CORRECT.
  
 11) THE 2003 SIMPSON CATALOG REQUIRES
 THE MSTM 20 TO BE ATTACHED TO THE
 EXISTING TIE BEAM WITH (4) 1/4"X 2-1/4"
 TITEN SCREWS AND (10) 10D NAILS INTO THE
 WOOD ROOF JOIST. PLEASE CORRECT.
  
 12) CHANGE THE TRUSS CONNECTOR SPECIFIED
 ON A1 FOR THE ROOF JOIST TO EXISTING
 BEAM FROM A TS-18 TO THE MSTM 20.
  
 13) THE ENGINEER'S TITLE BLOCK IS
 MISSING ON SHEET A1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202