| Date |
Text |
| 2003-03-31 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE ENERGY CALCULATIONS AS |
| | AS REQUIRED BY CHAPTER 13 OF THE FBC. |
| | |
| | 4) PROVIDE TWO COPIES OF A RECENT |
| | SURVEY. |
| | |
| | 5) LARGE MISSILE IMPACT PROTECTION IS |
| | REQUIRED FOR ALL NEW GLAZED OPENINGS. |
| | PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 6) THE WALL SECTION ON A2 SPECIFIES R-19 |
| | BLOWN INSULATION. THIS WILL NOT BE |
| | POSSIBLE WITH A SINGLE ASSEMBLY ROOF/ |
| | CEILING SYSTEM AS SHOWN. |
| | |
| | 7) THE SIMPSON TS-18 SPECIFIED ON A2 IS |
| | A WOOD TO WOOD CONNECTOR. PLEASE REVISE |
| | TO A WOOD TO MASONRY CONNECTOR SUCH AS A |
| | MTSM 20. SPECIFY THE FASTENERS AS LISTED |
| | IN THE 2003 CATALOG. |
| | |
| | 8) THE PLANS LIST 3636SH WINDOWS. PLEASE |
| | CLARIFY. ARE THESE H36 SINGLE HUNG |
| | WINDOWS AS THEY APPEAR TO BE ON THE |
| | ELEVATIONS? PROVIDE PRODUCT APPROVAL FOR |
| | THE WINDOWS AS SHOWN ON PLANS THAT WILL |
| | BE INSTALLED. |
| | |
| | 9) SPECIFY ON THE DRAWINGS WEATHER THE |
| | DOOR AT THE REAR OF THE EXISTING |
| | STRUCTURE IS EXISTING OR NOT. IF IT IS |
| | NEW PROVIDE PRODUCT APPROVALS. |
| | |
| | 10) THE NEW ADDITION CAN NOT BLOCK ANY |
| | EXISTING BED ROOM EGRESS WINDOWS OR BATH |
| | ROOM WINDOWS (UNLESS MECHANICAL VENT IS |
| | INSTALLED). IDENTIFY ON PLANS THE EXIST- |
| | ING ROOMS ADJACENT TO THE ADDITION. |
| | |
| | 11)THE WIRE MESH IN THE SLAB IS REQUIRED |
| | TO BE SUPPORTED ON APPROVED MATERIALS AT |
| | MAX. OF 3 FEET O.C. PER FBC 1909.3. |
| | INDICATE ON THE PLANS. |
| | |
| | 12) THE NEGATIVE WINDLOAD PRESSURES ARE |
| | INDICATED ON THE PLANS WITH POSITIVE |
| | SIGNS. PLEASE PLACE NEGATIVE SIGNS IN |
| | FRONT OF THE NEGATIVE PRESSURES ON A2. |
| | |
| | 13) INDICATE ON THE WALL SECTION THAT |
| | THE FOOTING IS REQUIRED TO BE A MINIMUM |
| | OF 12" BELOW GRADE AND THE FINISH FLOOR |
| | ELEVATION IS REQUIRED TO BE A MINIMUM OF |
| | 4" ABOVE FINISH GRADE. FBC 1804.1.3 AND |
| | CITY AMENDMENTS TO FBC 1804.1.7 |
| | |
| | 14) THE PLANS ARE REQUIRED TO HAVE A |
| | TITLE BLOCK WITH THE ENGINEER'S NAME, |
| | ADDRESS AND NUMBER. 61G15-23.002 |
| | |
| | 15) ADDITIONAL PERMITS WILL BE REQUIRED |
| | FOR ROOFING AND OTHER TRADES WITH |
| | ADDITIONAL FEES. |
| | |