Plan Review Notes
Plan Review Notes For Permit 03021815
Permit Number 03021815
Review Stop M
Sequence Number 4
Notes
Date Text
2003-10-09 00:00:00DENIED:
 1.MECHANICAL PERMIT REQUIRED.PLANS
 ORIGINALLY SUBMITTED INDICATED
 MECHANICAL PLANS WOULD BE SUBMITTED
 WITH MECHANICAL PERMIT APPLCIATION
 SEPARATELY.
  
 2.PLANS INDICATE CONDENSATE WILL
 TERMINATE INTO OPEN FLOOR DRAIN? PLEASE
 SEE ATTACHED CITY CODE SECTION 90-125,
 PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE.REVISE PLANS TO COMPLY.
  
 3.EQUIPMENT STANDS ON THE ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7, SEE
 ATTACHED.
  
 4.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER 2001 FBC(M) TABLE
 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.