| Plan Review Notes For Permit 03021815 |
| Permit Number |
03021815 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHTGA-1 TOILET ROOM DETAILS, SHOW | | | CLEAR FLOOR SPACE FOR LAVS. DOOR SHALL | | | NOT OPEN INTO THE CLEAR FLOOR SPACE OF | | | ANY FIXTURE. 114-22.2 | | | 2) SHT GP-1 GENERAL PLUMBING NOTES #6 & | | | WATER RISER DIAGRAM. AIR CHAMBERS ARE | | | NOT APPROVED. PLEASE DELETE REFERENCE & | | | REMOVE FROM RISER. 406.9 REQUIRES WATER | | | HAMMER ARRESTORS ON QUICK CLOSING VALVES | | | (WASH MACHINE, ICE MAKER, DISHWASHER). | | | IF WATER HAMMER ARRESTORS ARE USED, THEY | | | SHALL BE LOCATED NEAR THE FIXTURE NOT IN | | | CEILING PER PDI-WH 201 & MANUF. INSTALL- | | | ATION INSTRUCTIONS. | | | 3) ALL CAPPED/DEMO'ED PIPING SHALL BE | | | INSPECTED PRIOR TO COVERING. (PLEASE | | | ADD NOTE TO PLANS). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|