Plan Review Notes
Plan Review Notes For Permit 03021815
Permit Number 03021815
Review Stop P
Sequence Number 1
Notes
Date Text
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTGA-1 TOILET ROOM DETAILS, SHOW
 CLEAR FLOOR SPACE FOR LAVS. DOOR SHALL
 NOT OPEN INTO THE CLEAR FLOOR SPACE OF
 ANY FIXTURE. 114-22.2
 2) SHT GP-1 GENERAL PLUMBING NOTES #6 &
 WATER RISER DIAGRAM. AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE REFERENCE &
 REMOVE FROM RISER. 406.9 REQUIRES WATER
 HAMMER ARRESTORS ON QUICK CLOSING VALVES
 (WASH MACHINE, ICE MAKER, DISHWASHER).
 IF WATER HAMMER ARRESTORS ARE USED, THEY
 SHALL BE LOCATED NEAR THE FIXTURE NOT IN
 CEILING PER PDI-WH 201 & MANUF. INSTALL-
 ATION INSTRUCTIONS.
 3) ALL CAPPED/DEMO'ED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING. (PLEASE
 ADD NOTE TO PLANS).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377