| Plan Review Notes For Permit 03021803 |
| Permit Number |
03021803 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-12 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO PLANS AND RESUBMIT FOR REVIEW BEFORE | | | ROUGH INSPECTION. | | | | | | 1} WHERE IS PANEL "B"FED FROM? | | | | | | 2} SHOW LOCATION OF PANEL "B" ON PLAN. | | | | | | 3} DESIGNATE PANELS "A" & "B" ON | | | SCHEDULES. | | | | | | 4} AN EQUIPMENT GROUND IS REQUIRED | | | BETWEEN THE DISCONNECTS AND THE PANELS. | | | | | | 5} SHOW DISCONNECT LOCATIONS ON PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|