| Plan Review Notes For Permit 03021755 |
| Permit Number |
03021755 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-03 00:00:00 | ************ UNSAT ************* | | | | | | PLEASE SEE BOTH SETS OF PLANS. PLANS | | | DO NOTE CORRELATE, ONE SHOWS MORE RECEPT | | | -S/LTS, SW RECEPTS ETC. | | | | | | 1)NOTE: PLEASE HAVE PLANS REPRINTED | | | AND ALL CHANGES MADE TO PLANS. PLEASE | | | NOTE, CHANGES AN NOT BE DRAWN ON PLANS | | | UNLESS DONE BY ARCH OF RECORD AND "EACH" | | | CHANGE WOULD HAVE TO BE INITIALED,DATED | | | BY ARCH OF RECORD. FS 481 | | | | | | 2)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) ON PANEL SCHEDULE AS ON FIRST | | | REVIEW NOTES. | | | | | | 3)NOTE: PLEASE SEE FS 553.80(2)(B) FOR | | | PLANS AND DESIGN PROFESSIONAL. | | | | | | | | | PLEASE REPRINT AND HAVE PLANS SIGNED AND | | | SEALED BY THE ARCH OF RECORD 481.221 | | | AND SUBMIT FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|