Plan Review Notes
Plan Review Notes For Permit 03021755
Permit Number 03021755
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-12 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY EXISTING ELECT-
 RICAL.SHOW AS (E).
 RECEPT SPACING ETC.210-52
 FRONT AND REAR RECEPTS. 210-52E
  
 2)NOTE: SD`S REQ`D ON FIRST FLOOR
 LEADING TO LEVEL ABOVE AND PLEASE
 INCLUDE SD INSIDE AND OUTSIDE EXIST
 LOWER BEDROOM. NFPA-72 8-1.4.2
  
 3)NOTE: PLANS SHOW A MAIN DISC NEXT
 TO METER AND RISER SHOWS COMING FROM
 METER INTO A MCB PANEL? PLEASE CORRELATE
  
 4)NOTE: IF SERVICE IS NEW? PLEASE
 SUBMIT AIC RATING FOR NEW MAIN /MCB
 110-9
  
 5)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) PER 210-52D,210-11-C-3
  
 6)NOTE: PLANS REFERENCES PALM BEACH
 COUNTY EDITION OF FBC? PLEASE NOTE,
 2001 FBC. W/ CITY OF WEST PLAM BEACH
 AMENDMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372