| Plan Review Notes For Permit 03021755 |
| Permit Number |
03021755 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-12 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE CLARIFY EXISTING ELECT- | | | RICAL.SHOW AS (E). | | | RECEPT SPACING ETC.210-52 | | | FRONT AND REAR RECEPTS. 210-52E | | | | | | 2)NOTE: SD`S REQ`D ON FIRST FLOOR | | | LEADING TO LEVEL ABOVE AND PLEASE | | | INCLUDE SD INSIDE AND OUTSIDE EXIST | | | LOWER BEDROOM. NFPA-72 8-1.4.2 | | | | | | 3)NOTE: PLANS SHOW A MAIN DISC NEXT | | | TO METER AND RISER SHOWS COMING FROM | | | METER INTO A MCB PANEL? PLEASE CORRELATE | | | | | | 4)NOTE: IF SERVICE IS NEW? PLEASE | | | SUBMIT AIC RATING FOR NEW MAIN /MCB | | | 110-9 | | | | | | 5)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH CIRCUIT(S) PER 210-52D,210-11-C-3 | | | | | | 6)NOTE: PLANS REFERENCES PALM BEACH | | | COUNTY EDITION OF FBC? PLEASE NOTE, | | | 2001 FBC. W/ CITY OF WEST PLAM BEACH | | | AMENDMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|