Plan Review Notes
Plan Review Notes For Permit 03021749
Permit Number 03021749
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-07 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} RISER DIAGRAM OF THE NEW SERVICE.
  
 2} LOCATION OF NEW SERVICE, DON'T KNOW
 WHERE THE "UTILITY"ROOM OR BUILDING IS.
  
 3} PLEASE RESUBMIT DRAWINGS WITH MORE
 CLARITY REGARDING THE SCOPE OF WORK
 WITH ALL ROOMS IN PLACE ON ONE SHEET
 FOR ELECTRICAL.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 6} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 8} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 9} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 10} PLEASE SUBMIT LOAD CALCAULATION
 -S.PER 220,215-5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392