| Plan Review Notes For Permit 03021580 |
| Permit Number |
03021580 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-11 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | TO DRAWINGS AND RESUBMIT FOR REVIEW. | | | | | | 1} NOTE# 3(ELECTRICAL) ON SHEET "A-1" | | | REFERENCES # 12"TW"WIRE,BUT THE PANEL | | | SCHEDULE HAS #14 WIRE IN SOME | | | INSTANCES.PLEASE CLARIFY AND WAS THE | | | INDICATED "TW" DESIGNATION FOR THE | | | INSULATION TYPE INTENDED? | | | | | | 2} WHERE IS THE NEW ELECTRICAL PANEL IN | | | THE GARAGE BEING FED FROM? PANEL "A" | | | DOES NOT SHOW AN OCP FOR THAT PANEL. | | | | | | 3} PANEL "C" MUST COMPLY WITH ARTICLES | | | 250-32 & 225-31. | | | | | | 4} BATH CIRCUITS MUST COMPLY WITH | | | 210-11(C)(3). | | | | | | 5} KITCHEN COUNTERTOP RECEPTACLES MUST | | | COMPLY WITH 210-52(C)(1). | | | | | | 6} RECEPTACLES TO COMPLY WITH 210-8 | | | WHERE APPLICABLE,PLEASE INDICATE THE | | | SAME ON THE PLANS. | | | | | | 7} PLEASE COMPLY WITH | | | 210-70(A)(2),EXTERIOR DOOR EGRESS LIGHT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659 8096 EXT.8392 |
|