| Date |
Text |
| 2003-04-25 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE STRUCTURE IS LOCATED IN AN A5 |
| | FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. |
| | |
| | 3) SEPARATE PERMITS WILL BE REQUIRED FOR |
| | THE POOL. THE SOIL REPORT FOR THE POOL |
| | AND APPROVAL FROM PLANNING DEPT. SHOULD |
| | BE SUBMITTED AT THAT TIME. |
| | |
| | 4) THE SOIL BEARING TEST REPORT STATES |
| | THAT A SECOND STORY IS BEING ADDED TO AN |
| | EXISTING STRUCTURE. THE PLANS AND |
| | APPLICATION FOR PERMIT STATE THAT THE |
| | EXISTING STRUCTURE IS BEING DEMOLISHED |
| | (INCLUDING THE FOUNDATION) AND THAT A |
| | NEW TWO STORY RESIDENCE AND GARAGE/APT |
| | ARE TO BE BUILT. PLEASE CLARIFY. THE |
| | SOIL REPORT GIVES THE BEARING CAPACITY |
| | OF THE SOIL AS 1750 PSF AND THE |
| | STRUCTURAL PLANS REQUIRE 2500 PSF. THE |
| | SOIL REPORT ALSO INDICATES POSSIBLE |
| | SETTLEMENT OF UP TO ONE INCH. HAS THIS |
| | BEEN CONSIDERED IN THE DESIGN OF THE |
| | STRUCTURES. |
| | |
| | 5) PROVIDE A SOIL BEARING TEST FOR THE |
| | GARAGE/APARTMENT. |
| | |
| | 6) PROVIDE A CONSTRUCTION DETAIL FOR THE |
| | ARCHES AT THE B1 BEAMS OF THE BALCONIES. |
| | INDICATE THE LOCATION AND SIZE OF THE |
| | STEEL REINFORCING IF THEY ARE POURED |
| | CONCRETE. |
| | |
| | 7) STRUCTURAL SHEET 2 SPECIFIES 1/2" X |
| | 5" WEDGE ANCHORS TO FASTEN THE DOUBLE |
| | 2 X 10 LEDGERS TO THE BEAM AT THE |
| | BALCONIES. PLEASE REVIEW THIS FOR |
| | ADEQUATE EMBEDMENT DEPTH. |
| | |
| | 8) STRUCTURAL SHEET 2 ALSO INDICATES |
| | FLOOR TRUSSES AT THE FOYER WHICH IS OPEN |
| | TO SECOND FLOOR CEILING. PLEASE CORRECT. |
| | |
| | 9) INDICATE THE POSITIVE AND NEGATIVE |
| | WINDLOAD PRESSURES AT THE WINDOW AND |
| | DOOR OPENINGS OF THE GARAGE/APARTMENT. |
| | |
| | 10) THE POSITIVE AND NEGATIVE WINDLOAD |
| | PRESSURES THAT WERE RED LINED ON SHEETS |
| | A-3.0 AND A-3.1 NEED TO BE INITALED AND |
| | DATED BY THE DESIGNER OF RECORD. |
| | |
| | 11) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - WOOD FRONT DOOR |
| | - 3/4 HOUR FIRE RATED DOOR |
| | - OVERHEAD GARAGE DOOR |
| | |
| | 12) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE FRENCH DOORS AND THE TOWN AND |
| | COUNTRY STORM PANELS ARE EXPIRED. PLEASE |
| | SUBMIT CURRENT APPROVALS.(THE NEW REPORT |
| | FOR THE STORM PANELS IS #2304.) |
| | |
| | 13) SUBMIT MANUFACTURER'S SPECS. AND |
| | LISTING INFORMATION FOR THE PREFAB |
| | FIREPLACE UNDER SEPARATE PERMIT AS |
| | INDICATED BY THE ARCHITECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |