| Plan Review Notes For Permit 03021563 |
| Permit Number |
03021563 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | DENIED; | | | GARAGE APARTMENT SANITARY RISER | | | DIAGRAM; | | | 1.KITCHEN WASTE REQUIRES A MECHANICAL | | | VENT. | | | 2.DISHWASHER TO DISCHARGE INTO KITCHEN | | | WASTE. | | | 3.ONLY BATHROOM FIXTURES PERMITED ON | | | BATHROOM WET VENT. SEE SEC.909.1. | | | MAIN HOUSE SANITARY RISER DIAGRAM | | | 1.2ND FLOOR WASTE STACK CANNOT DUMP | | | INTO THE WET VENT FOR THE 1ST FLOOR | | | BATHROOM. | | | 2.1ST FLOOR VENT THRU WALL SHALL COMPLY | | | WITH 904.6. PLEASE ADD TO NOTES. | | | 3.SIZE 1ST FLOOR VENTS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|