| Date |
Text |
| 2003-03-12 00:00:00 | ************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE 210-52C-1 FOR KITCHEN |
| | COUNTERSPACE RECEPT SPACING. |
| | |
| | 2)NOTE: PLEASE SEE 210-8/ AND LOCAL |
| | AMENDMENTS, ALLL RECEPTS W/IN 6' OF ANY |
| | SINK TO BE GFI/GFI PROTECTED. (UTILITY |
| | ROOM). |
| | |
| | 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 |
| | MISSING SD AT LOWER LEVEL IN THE |
| | VICINITY OF STAIRWAY LEADING TO FLOOR |
| | ABOVE AND ON EACH LEVEL THERE AFTER. |
| | PLEASE ALSO SEE SAME FOR SD`S NOT |
| | PERMITTED IN KITCHENS AND MUST BE A MIN |
| | OF 3' FROM KITCHEN/BATHS. |
| | |
| | 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS |
| | MISSING PER 210-52 |
| | |
| | 5)NOTE: PLEASE SEE 210-70 FOR EGRESS LT |
| | PLEASE EITHER PROVIDE AUTOMATIC MEANS |
| | OF LIGHTING FOR STAIRWAY AT APT, OR |
| | 3-WAY SWITCH AT BOTTOM OF STAIRS. |
| | |
| | 6)NOTE: PLEASE SEE 225-31 FOR MEANS OF |
| | DISC AT DETACHED BLDG. PANEL "C" SHOWS |
| | MLO. MUST BE MCB OR PROVIDE DISC. |
| | |
| | 7)NOTE: PLEASE SIZE SERVICE ENT CONDUCT- |
| | ORS PER 310-16/310-15. PLEASE NOTE,EVEN |
| | W/ FUSES DOWN SIZING SERVICE, STILL SHOW |
| | -S A 475A TOTAL.PLANS SHOWS 4/0`S WHICH |
| | UNDER 310-15 ARE ONLY RATED FOR 250A'S |
| | PLEASE SEE LOAD IS SHOWN AT 282A'S. |
| | PLEASE SIZE ACCORDING TO 310-16. |
| | |
| | 8)NOTE: PLEASE LIST ALL REQ`D BATH |
| | CIRCUIT(S) PER 210-52D/210-11-C3 |
| | |
| | 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | CIRCUITS PER 210-12 |
| | |
| | 10)NOTE: PLEASE LIST/SHOW THE REQ`D WASH |
| | -ER CIRCUIT PER 220-16, 1500VA |
| | |
| | 11)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | AT MAIN HOUSE TO FOOTER STEEL AS REQ`D |
| | IN 250-50. SHOWN AT DETACHED BLDG OK. |
| | |
| | PLEASE REVIEW AND SUBMIT THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE |
| | ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |