| 2003-03-27 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SOIL BEARING REPORT FOR THE |
| | TWO STORY RESIDENCE AND THE GARAGE/APT. |
| | AS REQUIRED BY FBC 1804.2.2. |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR ALL EXTERIOR WINDOW AND |
| | DOOR OPENINGS. |
| | |
| | 5) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. IMPACT |
| | PROTECTION OR IMPACT RESISTANT GLAZING |
| | IS REQUIRED AT ALL EXTERIOR GLAZED |
| | OPENINGS. |
| | |
| | 6) SEPARATE PERMITS WITH ADDITIONAL FEES |
| | WILL BE REQUIRED FOR THE POOL, FENCES, |
| | ROOFING, ELECTRIC, MECHANICAL, PLUMBING, |
| | AND DRIVEWAY. |
| | |
| | 7) INDICATE ON THE PLANS THAT THE WIRE |
| | MESH IN THE SLAB IS TO BE SUPPORTED ON |
| | APPROVED MATERIAL AT 3 FEET ON CENTER |
| | MAXIMUM. SEE FBC 1909.3. |
| | |
| | 8)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 9) THE STRUCTURE IS LOCATED IN AN "A5" |
| | FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. CITY CODE REQUIRES THE |
| | LOWEST FLOOR TO BE ELEVATED TO SIX |
| | INCHES ABOVE THE BASE FLOOD ELEVATION. |
| | THE LOWEST FLOOR ELEVATION REQUIRED IS A |
| | MINIMUM OF 7.5 FT. ABOVE BASE FLOOD |
| | ELEVATION. PLEASE INDICATE THIS ON THE |
| | PLANS. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND UL LISTING INFORMATION FOR THE GAS |
| | FIREPLACE AND FLUE PIPE (IF REQUIRED). |
| | |
| | 11) SPECIFY THE ROOF SHEATHING FASTENING |
| | REQUIREMENTS AND ZONES ON THE PLANS. |
| | SEE CITY AMENDMENTS TO FBC TABLE 2306.1. |
| | NOTE: MEAN ROOF HEIGHT OF 25 FEET |
| | REQUIRES 8D RING SHANK NAILS IN ZONE 3. |
| | |
| | 12) SPECIFY ON THE PLANS THE REQUIRED |
| | 1-1/2" BLOCK RECESS IN THE SLAB AT THE |
| | EXTERIOR MASONRY WALL. CITY AMENDMENTS |
| | TO FBC 2111.1.9. |
| | |
| | 13) THE WALL TYPE ON A-1.0 LISTS 3/4" |
| | STUCCO AND THE WALL SECTION ON A-4.0 |
| | SPECIFIES 5/8" STUCCO. PLEASE CORRECT. |
| | |
| | 14) THE WINDOWS AT THE MASTER BATH TUB |
| | ARE REQUIRED TO BE SAFETY GLASS OR |
| | IMPACT RESISTANT GLAZING. SEE FBC 2405.2 |
| | |
| | 15) INDICATE THE LOCATIONS OF THE |
| | DRAFTSTOPPING AT THE FLOOR/CEILING |
| | ASSEMBLIES FOR THE RESIDENCE AND THE |
| | GARAGE/APT. FBC 2305.2.2 |
| | |
| | 16) THE WALL TYPES ON A-7 LISTS 3/4" |
| | STUCCO AND THE WALL SECTION ON A-7 LISTS |
| | 5/8" STUCCO. PLEASE CORRECT. |
| | |
| | 17) SUBMIT COMPLETE STRUCTURAL PLANS FOR |
| | THE GARAGE/APARTMENT. INCLUDE FOUNDATION |
| | WALL REINFORMENT, LINTELS, FLOOR FRAMING |
| | ROOF FRAMING, ROOF FRAMING, STAIRS, |
| | BALCONIES, ETC. |
| | |
| | 18) THE EXTERIOR EXIT STAIRS FOR THE |
| | GARAGE/APARTMENT DOES NOT COMPLY WITH |
| | FBC REQUIREMENTS. THE DOOR MUST OPEN TO |
| | A ROOFED OVER BALCONY, PORCH OR GALLERY |
| | NOT LESS THAN 4-1/2 FEET WIDE AND MUST |
| | BE LOCATED AT LEAST 10 FEET FROM |
| | ADJACENT PROPERTY LINES. THE STAIRS |
| | SHALL BE SEPARATED FROM THE INTERIOR OF |
| | THE BUILDING BY WALLS WITH A FIRE |
| | RESISTANCE RATING OF ONE HOUR WITH FIXED |
| | OR SELF-CLOSING OPENING PROTECTIVES AS |
| | REQUIRED FOR ENCLOSED STAIRS. SEE FBC |
| | 1006.2, 1006.2.2, 1006.2.4 |
| | |
| | 19) SPECIFY THE REQUIRED SPACING OF |
| | INTERMEDIATE AND BOTTOM RAILS FOR THE |
| | GUARDRAILS AT THE GARAGE/APARTMENT. |
| | |
| | 20) THE TIE BEAM AT THE COVERED PORCH ON |
| | THE FOUNDATION PLAN ON SHEET 1 ARE |
| | LABELED B1 AND THE TIEBEAM SCHEDULE |
| | LISTS TB-1. PLEASE COORDINATE. |
| | |
| | 21) THE LOCATIONS OF THE 6X6 POST ON |
| | STRUCTURAL SHEETS 2 & 3 DO NOT MATCH THE |
| | ARCHITECTURAL DRAWINGS FOR THE SECOND |
| | FLOOR COVERED BALCONY. |
| | |
| | 22) REVIEW THE CONNECTORS FOR THE 6X6 |
| | POSTS AT THE COVERED BALCONY. (HU 212-3 |
| | 1810# UPLIFT VALUE AND EPB 66 WITH 1500# |
| | UPLIFT VALUE) THE UPLIFTS GIVEN FOR THE |
| | TRUSSES APPEAR TO EXCEED THESE LIMITS. |
| | |
| | 23) SPECIFY THE CONNECTORS USED TO |
| | ATTACH THE 3-2X12 HEADERS AT THE COVERED |
| | BALCONY TO THE MASONRY WALLS OF THE |
| | STRUCTURE. |
| | |
| | 24) THE 2 SIMPSON HETAL 20 CONNECTORS |
| | SPECIFIED ON SHEET 3 HAVE AN UPLIFT |
| | RATING OF 2035# AND THE UPLIFT REQUIRED |
| | AT THE HIP GIRDERS IS 2853# AND 2291#. |
| | PLEASE CORRECT. |
| | |
| | 25) SPECIFY ALL REQUIRED CONNECTORS AND |
| | PROVIDE AN ANCHOR SCHEDULE FOR RESIDENCE |
| | AND GARAGE /APT. |
| | |
| | 26) PROVIDE STRUCTURAL DETAILS OF WHAT |
| | APPEARS TO BE A CONCRETE DECK EXTENSION |
| | (EYEBROW) AT THE COVERED BALCONY ON THE |
| | SECOND FLOOR. SEE WALL SECTION 1 ON A4.1 |
| | |
| | 27) PROVIDE DETAIL OF WATER PROOFING AT |
| | BALCONY FLOORS. |
| | |
| | 28) SPECIFY THE CONNECTIONS OF THE FLOOR |
| | TRUSSES TO THE DOUBLE 2 X 10 LEDGERS. |
| | INDICATE THE CONNECTORS AND FASTENERS. |
| | |
| | 29) PROVIDE DETAILS OF THE CONNECTIONS |
| | OF THE 2 X 10 FLOOR JOISTS TO THE |
| | LEDGERS AT THE SECOND FLOOR BALCONIES. |
| | INDICATE THE CONNECTORS AND FASTENERS |
| | FOR THE JOIST TO LEDGER CONNECTIONS AND |
| | THE FASTENERS AND SPACING FOR THE LEDGER |
| | TO MASONRY OR CONCRETE BEAM CONNECTIONS. |
| | |
| | 30) SPECIFY THE SIZE OF THE FLOOR JOISTS |
| | AT THE COVERED BALCONY. |
| | |
| | 31) INDICATE THE MATERIALS THAT WILL BE |
| | USED TO CLAD THE EXTERIOR CEILINGS AT |
| | THE COVERED PORCHES AND BALCONIES. |
| | |
| | 32) THE SECOND FLOOR FRAMING PLAN SHOWS |
| | JOISTS CANTILEVERED OVER WOOD BEAMS, |
| | WHICH IS INCONSISTANT WITH THE |
| | ARCHITECTURAL PLANS. PLEASE REVISE. |
| | |
| | 33) SEE ADDITIONAL NOTES ON ONE SET OF |
| | THE PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |