2003-03-04 00:00:00PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.EXISTING ATRIUM RETURN AIR DUCT
 THAT PENETRATES "TENANT SEPARATION"
 WALLS DO NOT INDICATE FIRE DAMPERS.
 CLARIFY IF THE FIRE DAMPERS ARE EXISTING
 OR IS THIS A PART OF AN EVAC SYSTEM...
 PLEASE CLARIFY.
 2.HP5 DOES NOT INDICATE A DUCT SMOKE
 DETECTOR.CLARIFY IF EXISTING, IT WILL
 BE REQUIRED IF THERE IS NOT ONE ALREADY
 INSTALLED.
  