| Plan Review Notes For Permit 03021543 |
| Permit Number |
03021543 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2004-03-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE #2 FEEDERS TO THE 200 AMP PANELS | | | ARE UNDERSIZED, SEE 310.16 NEC. | | | | | | 2} THE 2/0 FEEDERS TO THE DISCONNECTS | | | FROM THE METERS ARE INCORRECT PER | | | 310.16. | | | | | | 3} THE 200 AMP SERVICE IS A REVISION | | | FROM THE PREVIOUSLY SUBMITTED PLAN, | | | PL;EASE INDICATE IT AS A REVISION. | | | | | | 4} A 2ND PANEL AND DISCONNECT HAVE BEEN | | | ADDED,PLEASE INDICATE THEIR LOCATIONS ON | | | THE PLAN. | | | | | | 5} PLEASE GIVE A PANEL SCHEDULE FOR THE | | | 2ND PANEL. | | | | | | 6} PLEASE NOTE THAT THE CIRCUIT NUMBERS | | | ON THE PANEL SCHEDULE ARE NOT THE SAME | | | AS LISTED AT THE DEVICES, PLEASE | | | CORRELATE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|