| Plan Review Notes For Permit 03021543 |
| Permit Number |
03021543 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-09-22 00:00:00 | ******* NOTE REDLINED **** | | | | | | | | | PLANS STILL SHOW EMERGENCY AND EXIT LTS | | | ON THEIR OWN CIRCUITS,, PLEASE SEE | | | 700.12E. CIRCUIT WITH LIGHTING BRANCH | | | CIRCUIT. | | | | | | NEW PLANS WILL NEED TO HAVE HISTORIC | | | STAMP NEW SHEETS. |
|