| Plan Review Notes For Permit 03021543 |
| Permit Number |
03021543 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-05 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE. PANEL SCHEDULE IS SHOWING | | | 10 CIRCUITS FOR LIGHTING AND ONLY 10 | | | FIXTURES? THE SAME FOR RECEPTS. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATION PER | | | 220-3, 220-11, 220-13. | | | PLEASE SHOW ANY CONTINUOUS LOADS AT 125% | | | SHOWN AS RESIDENTIAL LOAD CALC. | | | 3)NOTE: PLEASE SHOW CONDUCTOR BETWEEN'MA | | | IN DISC AND PANEL. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW SERVICE EQUIPMENT BEING INSTALLED. | | | 110-9/215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATIONFOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|