| Plan Review Notes For Permit 03021485 |
| Permit Number |
03021485 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-03-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-2 RENOVATED HDCP TOILET ROOM | | | DOES NOT MEET CODE. MINIMUM OF 30" FROM | | | THE CENTER OF A WATER CLOSET TO THE | | | CENTER OF THE ADJACENT FIXTURE, (LAV). | | | SECTION 405.3.1. 18" TO CENTER OF W/C | | | OFF WALL - 30" TO CENTER OF LAV. - MIN. | | | 15" OFF WALL TO CENTER OF LAV. MINIMUM | | | OF 5'3" ROOM REQUIRED. | | | 2) SHT A-2 DOOR TO TOILET ROOM BEHIND | | | ELEVATOR SHALL NOT OPEN INTO THE CLEAR | | | FLOOR SPACE OF ANY FIXTURE OR UNOBSTRUC- | | | TED 5' TURNING RADIUS. | | | 3) PER 11-4.1.6(2) 20% ABOVE CONTRACT | | | PRICE SHALL BE SPENT ON ACCESSIBILITY | | | ISSUES. PLEASE INDICATE HOW $13,298 WILL | | | BE SPENT ON THIS REMODEL | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|