| Plan Review Notes For Permit 03021472 |
| Permit Number |
03021472 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-10-28 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND RISER DIAGRM NOTES. NOTES MENTION | | | 225A SERVICE AND RISER SHOWS 200A. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|