| Plan Review Notes For Permit 03021342 |
| Permit Number |
03021342 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-02 00:00:00 | THE DESIGN WIND PRESSURES FOR THE NEW | | | STOREFRONT DOOR ARE NOT SHOWN ON THE | | | PLAN AS REQUESTED ON THE 3/1/03 LIST. | | | | | | THE REQUEST REGARDING HANDICAP | | | ACCESSIBILITY HAS NOT BEEN ADDRESSED. | | | | | | THE GOLDBERG PLAN DATED 4/27/03 | | | ENUMERATES THREE ITEMS TO BE | | | ACCOMPLISHED UNDER THIS PERMIT.THE | | | PLAN SHOWS "NEW PLYWOOD ARCHES" THAT | | | ARE NOT INCLUDED ON THE LIST.PLEASE | | | CLARIFY THE SCOPE OF WORK. | | | | | | PROVIDE THE TEST AND/OR PRODUCT | | | APPROVAL FOR THE STOREFRONT SYSTEM. | | | | | | | | | AS PREVIOUSLY NOTED, $1500.00 IS TOO LOW | | | FOR THIS WORK.PROVIDE A COPY OF THE | | | SIGNED CONTRACT AND A DETAILED TAKEOFF | | | TO JUSTIFY THIS ASSERTION. |
|