| Plan Review Notes For Permit 03021333 |
| Permit Number |
03021333 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-21 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.LETTER FROM LANDLORD STATING TENANTS | | | OCCUPYING ADJACENT SPACE TO CITY PIZZA | | | IS AWARE THAT A GREASE DUCT RUNS THROUGH | | | THE SPACE.ACCESS TO MAINTAIN GREASE | | | DUCT WILL BE THROUGH THE ADJACENT SPACE. | | | | | | 2.PROVIDE MANUFACTURER SUBMITTAL DATA | | | & INSTALLATION INSTRUCTIONS ON THE IN- | | | LINE FAN. CLARIFY THAT FAN IS SUFFICIENT | | | TO MEET THAT FPM REQUIRED WITH THE | | | DISTANCE & 90 DEGREE OFFSETS INDICATED | | | ON THE PLAN. | | | | | | 3.SUBMITTAL/INSTALLLATION INSTRUCTIONS | | | FOR THE FIRE WRAP IS ALSO REQUIRED. |
|